Cookie Img
Home » Products » Single Phase Online UPS System » Single Phase Online UPS System

Single Phase Online UPS System

Single Phase Online UPS System
Product Code : 02
Product Description

Single Phase Online UPS System

High Performances High Efficiency
For the protection of telecommunication equipment, IT systems and mission critical systems like safety devices assuring maximum power reliability, Sentinel Power Green is the best and ideal solution.

State-of-the-art components and technology is employed for the design and development of Sentinel Power Green. It offers ideal protection to powered loads without having any affect on optimized energy savings and downstream systems. 

The series comprises 6 kVA single phase/ single and 8-20 kVA single-phase/single and three/single-phase models alone with online double conversion technology (VFI ). The load is powered consistently by the inverter that supplies a sinusoidal voltage stabilized and filtered in terms of voltage, frequency and form. Further immunity from lightning strikes and mains disturbances is offered by the provided input and output filters.

Sentinel Power Green is one of the best UPS available in the market today in terms of performance and technology. It has custom diagnostics, selectable economy mode functions, smart active mode functions, USB and RS232 interfaces with PowerShield³ software, LCD Display, ESD input and interface slot with optional boards.

High UPS reliability:

  • Complete microprocessor control
  • Interruption-free manual and static bypass.
  • Specifications assured up to 40 °C (the engineers have designed the components to operate at high temperatures and hence take less stress at normal temperatures).

Parallelable:

  • Power arrangement of 3 units for (N+1) power parallel system or redundant. The UPS Continue to work in parallel even when the connection cable is disturbed (Closed Loop).

Operating mode selection:

With the help of software or manually through front display panel, the operating mode can be programmed.

  • For critical applications On line double conversion Mode is provided
  • To increase efficiency by up to 80% economy mode is offered. To power low priority loads It allows the choosing of Line Interactive technology (VI) from the mains supply
  • Based on the superiority of mains power supply, the UPS decides to choose between the operating mode (VFI or VI).
  • (50 or 60 Hz) Frequency converter operation
  • For emergency needs the UPS can be made to operate on the failure of mains power supply (emergency only mode).

High quality output voltage:

  • With even non-linear loads e.g. IT loads along with a crest factor of up to 3:1
  • Strong short circuit current on bypass.
  • High overload capacity even with mains failure up to 150% by inverter
  • Stabilized, Filtered, and reliable voltage (VFI double conversion on-line technology in compliance with EN 62040-3. Filters are given for the suppression of atmospheric disturbances
  • Close to 1 UPS input power factor and sinusoidal current uptake.

Simplified installation:

  • UPS is able to be installed on a three-phase or single-phase distribution network
  • FPR powering local consumers, output terminal board +2IEC sockets is provided( modems, computers, etc.)
  • Built in castors simplified positioning

High battery reliability

  • Manual and automatic battery test
  • For ensuring right UPS operation in emergency conditions and for obtaining the best performance, proper battery care is essential. To optimize battery care system the Riello UPS battery care system comprise of a series of capabilities and features.
  •  Employing matching Battery Boxes run time can be extended unlimited
  • When the input supply is somewhere between 84V to 276V or during mains failure of below 40 ms, the batteries do not cut.


Low impact on the mains

  • Sinusoidal uptake of input current on single-phase series.

Other features:

  • enhanced diagnostics: measurements, alarms and status available on custom LCD display
  • Less noise (<40 DBA ): Due to its PWM load-dependent digitally controlled fan and high frequency switching inverter, it can be installed in any atmosphere.
  • Auto restart (programmable via software, automatically mains supply is restored or display panel)
  • Emergency Function: Only on the failure of mains power supply the UPS can be selected to work
  • Standard Back-Feed Protection: to save energy from getting fed back to the network.
  • Flash upgradable UPS digital updating

Technical Specification

Models

SPM 6

SPH 8

SPH 10

SPH 10 ER

INPUT

Voltage

220-230-240 Vac

220-230-240 Vac

220-230-240 Vac

220-230-240 Vac

Frequency

50/60 Hz +/- 10 Hz

50/60 Hz +/- 10 Hz

50/60 Hz +/- 10 Hz

50/60 Hz +/- 10 Hz

BY PASS

Voltage tolerance

160 - 276 Vac (selectable in Economy Mode or Smart Active Mode)

160 - 276 Vac (selectable in Economy Mode or Smart Active Mode)

160 - 276 Vac (selectable in Economy Mode or Smart Active Mode)

160 - 276 Vac (selectable in Economy Mode or Smart Active Mode)

Frequency tolerance

Selected frequency ±10%

Selected frequency ±10%

Selected frequency ±10%

Selected frequency ±10%

OUTPUT and INVERTER OUTPUT

Rated power

6000 VA

8000 VA

10000 VA

10000 VA

Active power

5400 W

7200 W

9000 W

9000 W

Waveform (Battery Mode)

Sinusoidal

Sinusoidal

Sinusoidal

Sinusoidal

OVERLOAD TIMES

100% < Load < 110%

5 min

5 min

5 min

5 min

100% < Load < 120%

1 min

1 min

1 min

1 min

125% = Load < 150%

10 sec

10 sec

10 sec

10 sec

Load = 150%

0,1 sec

0,1 sec

0,1 sec

0,1 sec

BATTERIES

Type

VRLA AGM maintenance-free lead based

VRLA AGM maintenance-free lead based

VRLA AGM maintenance-free lead based

VRLA AGM maintenance-free lead based

Recharge time

6-8 hours

6-8 hours

6-8 hours

6-8 hours

ENVIRONMENTAL

Color

Dark grey RAL 7016

Dark grey RAL 7016

Dark grey RAL 7016

Dark grey RAL 7016

Safety compliance

EN 62040-1:2008; EN 62040-1/EC:2009; EN 62040-1/A1:2013 and Directive 2014/35/EU

EN 62040-1:2008; EN 62040-1/EC:2009; EN 62040-1/A1:2013 and Directive 2014/35/EU

EN 62040-1:2008; EN 62040-1/EC:2009; EN 62040-1/A1:2013 and Directive 2014/35/EU

EN 62040-1:2008; EN 62040-1/EC:2009; EN 62040-1/A1:2013 and Directive 2014/35/EU

EMC conformance

EN 62040-2 and Directive 2014/30/EU

EN 62040-2 and Directive 2014/30/EU

EN 62040-2 and Directive 2014/30/EU

EN 62040-2 and Directive 2014/30/EU

Protections

Overcurrent - short-circuit - overvoltage - undervoltage - temperature - excessive low battery

Overcurrent - short-circuit - overvoltage - undervoltage - temperature - excessive low battery

Overcurrent - short-circuit - overvoltage - undervoltage - temperature - excessive low battery

Overcurrent - short-circuit - overvoltage - undervoltage - temperature - excessive low battery

Line-Interactive/Smart Active efficiency

98%

98%

98%

98%

Noise

40 dBA at 1 m

56 dBA at 1 m

56 dBA at 1 m

56 dBA at 1 m

Operating temperature

0°C / +40°C

0°C / +40°C

0°C / +40°C

0°C / +40°C

DATA

Weight

63 Kg

78 Kg

84 Kg

28 Kg

Dimensions (h w d)

708x262x557 mm

708x262x557 mm

708x262x557 mm